In the present work the effect of Corrosion & Scale Inhibitor was evaluated by using of the commercial product (Kurita S2050) that mainly containing of (Na2HPO4) sodium phosphate as corrosion inhibitor and (C6H11NaO7) sodium glocunate as scale inhibitor & dispersant. The dosing rate of this chemical was controlled according to the treatment system depend mainly on the monitoring of LI & RI indexes for (30) days treatment in the cooling tower unit of Al-Dora Oil refinery-Baghdad. The corrosion rate and the corrosion inhibitors efficiency were calculated by measurement of weight loss in standard test coupon (AISI 1010). After 30 day of the Field Test, the result show that the treatment program performance was effective in the corrosion & scale inhibition through an acceptable corrosion rate less than 0.018 in gmd. Also the result of corrosion rate was analyzed statistically by using of (ANN) to formulate a prediction equation to corrosion rate identification.
Downloads
Downloads
Published
Issue
Section
License
The authors retain the copyright of their manuscript by submitting the work to this journal, and all open access articles are distributed under the terms of the Creative Commons Attribution-NonCommercial 4.0 International (CC-BY-NC 4.0), which permits use for any non-commercial purpose, distribution, and reproduction in any medium, provided that the original work is properly cited.